Building Regulations Part K: Non-HRB Domestic Compliance Guide for Small Practices

Approved Document K — Protection from Falling, Collision and Impact · Building Safety Act 2022 · Non-HRB projects

Summary

What the Building Safety Act requires for Part K on non-HRB domestic jobs

Requirements K1–K6 cover stairs, ladders and ramps; falling protection; vehicle barriers; and glazing impact safety. On domestic work the stair is where design ambition meets regulation: every loft conversion lives or dies on whether a compliant stair can be threaded into the plan with 2 m headroom (1.9 m at centre / 1.8 m at the low side is accepted for loft conversions where the stair rises into the roof).

As Principal Designer (BSA), your evidence is dimensional: a stair section proving pitch, rise/going and headroom at Stage 3, guarding heights and baluster spacing (no 100 mm sphere passing through) on the Stage 4 details, and safety glazing marked on the fenestration schedule. These are exactly the items Building Control measures on site, so the drawing record protects you when the joiner improvises.

Note the boundary with Part M: Part K governs the safety geometry of private stairs, while Part M layers access requirements on top. Where both apply, the more onerous provision wins — design to the combined envelope, not to one document.

Key design risks and evidence needed (RIBA Stages 2–4)

Standards and references you should be citing

Domestic stair and guarding dimensions at a glance

ElementRequirement (private dwelling)Where it bites
Stair pitchMaximum 42°; rise ≤220 mm, going ≥220 mmLoft conversions, tight plans
Headroom2.0 m; loft conversions 1.9 m centre / 1.8 m edgeStairs rising into roof slopes
Handrail900 mm above pitch line; both sides if width ≥1 mAll stairs with a drop
Guarding (internal)900 mm, no 100 mm sphere gap, 0.36 kN/mLandings, galleries, open wells
Guarding (external/Juliet)1,100 mmBalconies, terraces, Juliet balconies
Safety glazingBelow 800 mm; below 1,500 mm at doors and side panelsGlazed doors, low-level glazing, wet rooms

Common pitfalls that catch out sole practitioners

Frequently asked questions

What headroom is acceptable on a loft conversion stair?

The general requirement is 2 m measured vertically from the pitch line. For loft conversions, Approved Document K accepts 1.9 m at the centre of the stair width reducing to 1.8 m at the side where the stair passes under the roof slope. Prove it with a drawn section — it is the single most common loft feasibility killer.

When are alternating tread (space-saver) stairs allowed?

Only for access to a single habitable room (plus, at most, an associated bathroom/WC that is not the only one in the dwelling), and only where there is genuinely not enough space for a conventional stair. They need handrails both sides and slip-resistant treads.